Характеристики
Описание товара
Parameter
Functions:
1.Over-voltage protection
2.Under-voltage protection
3.Automatic recovery
4.Voltage display(voltage measurement)
5.Voltage Correction
Product Parameters:
1.Model number:TVPS1-40A
TVPS1-63
A
2.Power supply:230VAC 50/60Hz
3.Max.Loading power:40A/63A
4.Over-voltage protection value range:230V~300V
-OFF
Over-voltage recovery voltage range:225V--295V
Over-voltage protection action time:0.1s~30s(default value:0.5s)
Over-voltage r
ecovery delay time:1s~500s(default:30s)
5.Under-voltage protection value range:140V--210V --OFF(default:170V)
Under-voltage recovery voltage range:145V--215V (default:190V)
Under-voltage protection action time:0.1s~30s(default:0.5s)
Under-voltage
r
ecovery delay time:1s~500s(default:30s)
6.Power-on delay time:1s~500s
7.Power consumption : <2W
8.Electric machinery life : 100,000 times
9.Installation:35mm DIN rail
Noted: When you first connect the product, you have to wait about 10 second(
Power-on delay time:1
s~50
0s(default:10
s)),
after the red light turn off, then the product will work.
Product Display